46
Appendix A: Approximate Back-up Time Table
Model Load (VA) Backup Time @ 24Vdc 100Ah (min) Backup Time @ 24Vdc 200Ah (min)
X-4KW-M
300 449 1100
600 222 525
900 124 303
1200 95 227
1500 68 164
1800 56 126
2100 48 108
2400 35 94
2700 31 74
3000 28 67
3300 25 59
3600 22 50
4000 17 38
Note: Backup time depends on the quality of the battery, age of battery and type of battery.