Error code
Error
code
Description of error
Priority
0 No error
10 Outside temperature sensor error 6
20 Boiler temperature 1 sensor error 9
25 Solid fuel boiler temperature (wood) sensor error 9
26 Common fl ow temperature sensor error 6
28 Flue gas temperature sensor error 6
30 Flow temperature 1 sensor error 6
32 Flow temperature 2 sensor error 6
38 Flow temperature primary controller sensor error 6
40 Return temperature 1 sensor error 6
46 Return temperature cascade sensor error 6
47 Common return temperature sensor error 6
50 DHW temperature 1 sensor error 9
52 DHW temperature 2 sensor error 9
54 DHW primary controller sensor error 6
57 DHW circulation temperature sensor error 6
60 Room temperature 1 sensor error 6
65 Room temperature 2 sensor error 6
68 Room temperature 3 sensor error 6
70 Buffer storage tank temperature 1 sensor error 6
71 Buffer storage tank temperature 2 sensor error 6
72 Buffer storage tank temperature 3 sensor error 6
73 Collector temperature 1 sensor error 6
74 Collector temperature 2 sensor error 6
81 Short-circuit LPB 6
82 LPB address collision 3
83 BSB wire short-circuit 6
84 BSB address collision 3
85 BSB radio communication fault 6
98 Extension module 1 fault (common fault status message) 6
99 Extension module 2 fault (common fault status message) 6
100 2 clock time masters (LPB) 3
102 Clock time master without backup (LPB) 3
105 Maintenance message 5
109 Boiler temperature supervision 9
110 Lockout by SLT 9
6.21 List of displays
Priorities are assigned to pending errors. From priority 6, alarm messages are delivered,
which are used by remote supervision (OCI). In addition, the alarm relay will be set.