9.5 Boiler cleaning
Shut off the operation switch before carrying out any service or maintenance on boiler
or peripheral equipment.
The combustion chamber of the boiler is easily cleaned from the front:
Deactivate operating switch.
Remove hood.
Remove euro plug for burner.
Loosen the screws of the cleaning door. The door can now be swivelled out with out
dismounting the burner.
Remove turbulators.
Clean combustion chamber and heat recovery adjuncts with supplied cleaning brush.
After cleaning refit the turbulator, close the cleaning door again and evenly tighten
the screws.
Reconnect the euro plug of the burner.
Refit the hood.
Activate operating switch.
The boiler cleaning must be performed according to existing regulations..
9.6 Spiro-Condens system cleaning
In normal operation the Spiro-Condens system is self-cleaning. For recurring
operation faults and increasing flue gas temperatures, it is probably necessary to clean
the spiral finned tube of the flue gas heat exchanger. The cleaning is performed by rins-
ing or for very severe dirt by removing the spiral finned tube and cleaning.
The boiler must be disconnected from the mains when cleaning it.
Standard cleaning - once a year in connection with maintenance (regular checks, boiler
cleaning, etc.) recommended:
1. Deactivate operating switch.
2. Remove rear cover plate.