Warning
4
1. GENERAL
1.1 War nings
- The manual must be read before installation and start-up.
- This manual should be followed by anyone who for any reason performs
work on the installation or its component parts.
- The manual is to be considered as part of the burner and must always
be kept in the vicinity of the installation site.
- Ensure that the fresh air inlet to the room where the burner is located is
always open.
- The burner may only be installed by authorized personnel.
- The burner is designed for oil viscosities ranged between 1.2 and 8.0
cSt at 20°C.
- No burner safety system may be disconnected.
- Cut the power and shut-off the fuel supply before performing service.
- Enertech recommends that the burner be shut down when the oil tank
islled,andforsixhoursthereafter,toreducetheriskofblockages.
- Ensure that the burner is protected from water spills, as its design will
not withstand such.
- Oilltersshouldbeused.
- Only use spare parts recommended by Enertech.
Assembly and Service - Filtersmustbettedtotheoilsupplyline.
- Shut-offcocksmustbettedtotheoilsupplyline.
- Oil lines must adhere to the current national standards of each respective
country.
Adjusting the burner
Inordertoachievecorrectadjustmentuegasanalysisandtemperature
measurements must be carried out. Otherwise there is a risk of soot
build-up,poorefciencyorcondensateprecipitationintheue.
3-4
14-16
19-21
ø20/24
ø87
5
2. TECHNICAL DATA
2.1 Model BF1 M1V 87-20/BF1 M1V 87-24
Factory setting
Boiler Burner Burner Output Air Nozzle assembly Oil pressure Nozzle
kW bar
CTC 380IC17 BF1M1V 87-20 17, 8 5 5 10,8 0,40x80°S
CTC 380IC19 BF1M1V 87-20 19,7 4 13 11,4 0,45x80°S
CTC 380IC24 BF1M1V 87-24 24,5 7 12 10,2 0,55x80°S
CTC 380IC29 BF1M1V 87-24 29,3 15 12 10,2 0,65x80°S