◆Multi-functions relay setting
Description: Set multi-functions output contactor function.
Cd29 (TIME): This function must accommodate Cd47, 48=0 setting. When motor starts operation, the time
counter is active.
Cd45 (Frequency detect level) : accommodate Cd47, 48=6, Cd45 will appoint the action level.
1
CD45
FA-FC
OPEN
CLOSE
Time
HZ OUTPUT
Time
Cd47, 48 could be set the function by Multi-functions ouput contactor, please refer to the list:
Setting Function
0 Time counter (accommodate Cd29)
1 Fault
2 Stop
3 Acceleration
4 Speed reached
5 Deceleration
6 Frequency reached (operation frequency>Cd45)
7 Current reached (compare to Cd85 and Cd86 value)
8 Over heating prediction action(Cd82×Cd84)
9 OL fault action
10 No action
9. Output/ input terminals
Constant
No.
Constant name Settable range Factory setting
Change during
operation
Cd29 TIME 0󲕏60000 5 X
Cd45 Frequency detect level 0.00󲕏400.00 0.50 X
Cd47 Multi-functions relay 1 0󲕏10 1 X
Cd48 Multi-functions relay 2 0󲕏10 1 X
Cd49 Multi-functions relay DO 0󲕏10 8 X