14. Protective function ■
◆Stall prevention limit during constant speed
Description:A heavy load is placed on the motor when constant operation and makes inverter output current
exceed Cd74 setting value. The inverter will automatical reduce output frequency to prevent the motor from
stall (OC/OL). When a load disappeared or lightened and makes inverter output current be samller than Cd74
setting value. The inverter will automatical accelerate to work frequency.
Cd73= 0, invalid
= 1, valid, decelerated by Cd11 deceleration time.
Cd74 setting method: Set 100% as inverter rated current.
Constant
No.
Constant name Settable range Factory setting
Change during
operation
Cd73
Stall prevention selection during constant
speed operation
01 1 X
Cd74
Stall prevention level during constant
speed operation
30200 125% X
Cd74
Output current
Time
Output frequency
Time
To avoid stalling to proceed deceleration