5.2 Installation
Follow the instructions found in section 3.3 for mounting the enclosure. The relay box must be
mounted directly to the right and within 6 inches of a repeater as shown in figure 6. Power down the
AR-5 repeater then connect the jumper cable P/N CA-12i0-2810 from J3 on the AR-5 repeater board
to J1 on relay board #1 in the relay box. Warning: The relay box may be damaged if the power is
not removed from the repeater prior to connecting it to the relay box. The cable must be run in
conduit. Cable connections are keyed to insure proper connection. The relay box will not function
without this cable connected.
5.2.1 Wiring
Refer to figures 6 and 7 for wire routing and relay connections. The terminal blocks are of the plug in
type in order to make wiring easier. Simply connect the wires to the terminal blocks while unplugged
and then insert them into the appropriate locations to make the relay connections. Follow all NFPA
and local electrical codes when wiring this product. Acceptable wire size is 16-22 awg. Relay box
outputs are to be connected to power limited circuits only. Relay contacts are rated at 24Vdc 1A
resistive.
5.2.2 Programming
Many programming options are available for the relay unit. Since relay activation and deactivation is
programmed at the CP-3600(+) control panel, please refer to that manual for programming options
and instructions.