7.2 Existing Installation Survey
To check the signal of an existing device in an installation, momentarily place a magnet in the
appropriate survey location of the device. Refer to the device manual for the survey location of each
type of transmitter. One beep should be heard at the device and the repeater which received the
survey signal followed by either a single beep or two beeps at the device only. A single beep
indicates an unacceptable survey and two beeps indicate an acceptable survey. If an unacceptable
survey is the result, the device will have to be relocated or a repeater added to receive it at this
location. To test repeater to repeater communications, press the survey button located on the
repeater circuit board for 1 second then release. Refer to figure 3 for the survey button location. The
beeps that indicate the survey start and result are the same as a device. The repeater which received
the survey signal will beep once. This is to notify the installer which repeater is responding to the
device survey signal. A minimum of 5 consecutive successful surveys with the repeater held in the
mounting location must be accomplished to validate the location as acceptable for mounting the
device.