P/N IM-AR5 Rev. F
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision date and are subject to change without notice.
10
Section 3 - Installation
3.1 Preparing the Installation Site
Prior to the installation of an AR-5 repeater a signal survey must be performed by a factory trained
technician or authorized dealer. The signal survey determines the locations of the repeaters in order
to receive the devices. Refer to the Signal Survey section in this manual and individual CWSI device
manuals for the proper method to conduct a signal survey. The completed survey becomes the
blueprint layout for the actual installation.
During the survey, try to locate AR-5 repeaters close to available 120/240 VAC uninterruptible power.
All AR-5 connections must be installed in conduit. When connecting primary A/C power always follow:
1- National Fire and Electrical Codes (NFPA 72 and NFPA 70)
2- Local Electrical and Fire Code requirements
3- Local AHJ (Authority Having Jurisdiction) requirements
WARNING: Make sure A/C supply is turned OFF prior to connecting the AR-5 repeater.
3.2 Receiving and Unpacking the Equipment
Upon receiving the equipment, the carton should be inspected for damage, which may have occurred
during shipment. Each package should be checked against the packing slip for completeness.
Differences should be reported to CWSI immediately. If any product is suspected of damage it should
be checked for proper operation or returned to CWSI.
3.3 Installing the AR-5 Repeater
WARNING: This equipment must be professionally installed by factory trained personnel. Use
of an antenna other than listed in the compatibility section of this manual may be harmful to
persons, void FCC or damage the equipment.
The AR-5 repeater unit must be enrolled into the CP-3600(+) control panel to function properly. This
will validate the repeater as being part of the installation and allow the installer to program relay
outputs, unit description etc. as needed for the installation. Note: Always attach a compatible
antenna to both repeater sma connectors A and B prior to applying power to the repeater,
enrolling the repeater or conducting a signal survey. There are three antennas available for use
with the AR-5 repeater. The differences are the type and gain. The OM-1 Omni antenna should be
used except where installation space restrictions are an issue. The OM-2 Omni will have slightly
lower gain and is shorter which may be helpful in space restricted areas. The OM-3 will have
increased range over the OM-1&2 where longer omni directional reception is needed. The YA-1 is a
directional Yagi antenna with high gain for signal reception at longer distances. Typical antenna
configurations are shown in figure 1A.
To install the YA-1 follow these steps:
1. Perform a signal survey to determine an acceptable indoor location.
2. Attach the mounting brackets to a suitable surface.
3. Fasten the 24” mast to the mounting brackets and tighten the nuts.
4. Attach the YA-1 to the top of the mast and make sure the elements are in a vertical
position.
5. Aim the antenna towards the desired reception location making sure none of the elements
make contact with any surrounding surfaces or objects then tighten the antenna bracket.