Using Trends – Too Much Cooling (example)
ZONE TEMPERATURE
Morning A/C comes on
Temp keeps dropping, even below
setpoint
DELTA SETPOINT MINUS ZONE TEMP
Temperature way too cold, much below
setpoint most of the day
BRANCH PRESSURE
Thermostat is trying to compensate for
over cooling all day long.
SETPOINT TEMPERATURE
•1
st
DR Event bumped up setpoint 2 deg
•2
nd
DR Event bumped up additional 2 deg
•Completion of Event – back to normal
Causes/Remedy:
•Faulty Reset Velocity Controller
•VAV Box Fault
•Adjacent Zone Overcooling