Survey Checklist : Step 1 – HVAC system info
Questions/Info request Information
Details of compressed air system
Type of HVAC system (single duct, VAV, hot-deck, cold-
Power and network connection verification
Remember
• The WPT thermostats are zone control only
• The thermostat controls the terminal unit in the same exact way as the old Johnson or Honeywell
pneumatic thermostat.
• For terminal units having both heating and cooling controls (i.e fan coil unit, VAV w/ reheat),
consider using the WPT deadband thermostat.
• The WPT thermostat has an standard pneumatic thermostat built inside. Like any pneumatic
thermostat, this is a proportional control device only. The WPT does not have integral reset (PI
control) parameters.