Cypress Confidential
Best practices
When you have locations with multiple GBC make sure you use different
Network ID numbers on each GBC.
- Even buildings within 1000ft may receive crosstalk
Many times the core will be cool only and perimeter will have cooling with
reheat requiring different thermostat types. Both should be checked.
If a section of a building has been remodeled check thermostats to verify
type (direct acting or reverse acting).
Locating the GBC in the center of the building close to power and a LAN.
ID assignments
WPT
- Useful to number per floor or area (1xxx = 1
st
floor, 2xxx = 2
nd
floor…)
- If possible, number in a clock-wise manner through the floor or some other
logical pattern to help with maintenance
RWAL
- Left most digit doesn’t matter, but right most digit should be numbered with
the lower number closest to the Hub
Repeaters with an ID ending with 1 will be discovered first
Do not repeat the right most digit in a repeater ID number for a given network