OMM 1130 65
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a compressor after it
has stopped. Start-Start is the time required before starting a compressor after the last time it has started.
It is recommended that the default values of 5 minutes and 15 minutes not be changed.
SET COMP SPs (2)
InterStgUp =XXXsec
InterStgDown= XXsec
Clear Cycle Tmr = NO
InterStageUp is the time delay since the last stage change before a compressor can stage on, default is 120
sec.
InterStageDn is the time delay since the last stage change before a compressor can stage off normally (not
by an alarm). Default is 30 sec. It is recommended that these settings not be changed.
# of Compressors = 4 # of Compressors = 6
SET COMP SPs (3) SET COMP SPs (3)
Comp 1 = Enable Comp 1 = Enable
Comp 3 = Enable Comp 3 = Enable
Comp 5 = Enable
# of Compressors = 4 # of Compressors = 6
SET COMP SPs (4) SET COMP SPs (4)
Comp 2 = Enable Comp 2 = Enable
Comp 4 = Enable Comp 4 = Enable
Comp 6 = Enable
Enable screens #3 and #4 require the manager password to change.
TGZ Units Only (R134a)
SET COMP SPs (5) SET COMP SPs (5)
Expansion Valve Expansion Valve
Type = Thermal Type = Electronic
MaxOpPress=XXX.X psi
Expansion Valve Type = Electronic
SET COMP SPs (6)
Cir 1 EXV
EXV Control = Auto
Manual EXV Pos=XXX.X
Expansion Valve Type = Electronic
SET COMP SPs (7)
Cir 2 EXV
EXV Control = Auto
Manual EXV Pos=XXX.X
Expansion Valve Type = Electronic Only
SET COMP SPs (8)
SuperheatTarg= XX.X