6 Configuration
Installation manual
22
ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P586454-1 – 2019.07
Availability
The weather-dependent curve is available for:
Main zone - Heating
Main zone - Cooling
Additional zone - Heating
Additional zone - Cooling
Tank
INFORMATION
To operate weather dependent, correctly configure the
setpoint of the main zone, additional zone or tank. See
"6.3.4Using weather-dependent curves"[423].
6.3.2 2-points curve
Define the weather-dependent curve with these two setpoints:
Setpoint (X1, Y2)
Setpoint (X2, Y1)
Example
Y1
Y2
X1 X2
a
Item Description
a Selected weather dependent zone:
: Main zone or additional zone heating
: Main zone or additional zone cooling
: Domestic hot water
X1, X2 Examples of outdoor ambient temperature
Y1, Y2 Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:
: Underfloor heating
: Fan coil unit
: Radiator
: Domestic hot water tank
Possible actions on this screen
Go through the temperatures.
Change the temperature.
Go to the next temperature.
Confirm changes and proceed.
6.3.3 Slope-offset curve
Slope and offset
Define the weather-dependent curve by its slope and offset:
Change the slope to differently increase or decrease the
temperature of the leaving water for different ambient
temperatures. For example, if leaving water temperature is in
general fine but at low ambient temperatures too cold, raise the
slope so that leaving water temperature is heated increasingly
more at decreasingly lower ambient temperatures.
Change the offset to equally increase or decrease the
temperature of the leaving water for different ambient
temperatures. For example, if leaving water temperature is always
a bit too cold at different ambient temperatures, shift the offset up
to equally increase the leaving water temperature for all ambient
temperatures.
Examples
Weather-dependent curve when slope is selected:
X1 X2
c
d
e
Y1
Y2
Y3
Y4
a b
Weather-dependent curve when offset is selected:
Y1
Y2
Y3
Y4
X1 X2
a b
c
d
e
Item Description
a WD curve before changes.
b WD curve after changes (as example):
When slope is changed, the new preferred
temperature at X1 is unequally higher than the
preferred temperature at X2.
When offset is changed, the new preferred
temperature at X1 is equally higher as the preferred
temperature at X2.
c Slope
d Offset
e Selected weather dependent zone:
: Main zone or additional zone heating
: Main zone or additional zone cooling
: Domestic hot water
X1, X2 Examples of outdoor ambient temperature
Y1, Y2,
Y3, Y4
Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:
: Underfloor heating
: Fan coil unit
: Radiator
: Domestic hot water tank