10 | Configuration
Installer reference guide
186
EPRA14~18D + ETVH/X16S18+23E
Daikin Altherma 3 H HT F
4P644737-1A – 2022.03
In case of Schedule only or Schedule + reheat domestic hot water
preparation, the storage comfort temperature is weather-dependent (according to
the weather-dependent curve), the storage economic and reheat temperature are
NOT weather-dependent.
In case of Reheat only domestic hot water preparation, the desired tank
temperature is weather-dependent (according to the weather-dependent curve).
During weather-dependent operation, the end-user cannot adjust the desired tank
temperature on the user interface. Also see "10.4 Weather-dependent
curve"[4146].
# Code Description
[5.C] [0-0E]
[0-0D]
[0-0C]
[0-0B]
WD curve:
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E] [0-0D]
▪ T
DHW
: The desired tank temperature.
▪ T
a
: The (averaged) outdoor ambient
temperature
▪ [0-0E]: low outdoor ambient temperature: –
40°C~5°C
▪ [0-0D]: high outdoor ambient temperature:
10°C~25°C
▪ [0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature:
- 45°C~[6‑0E]°C (for E models)
- min(45, [6‑0E])°C~[6‑0E]°C (for E7 models)
▪ [0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C
Margin
In domestic hot water operation, the following hysteresis value can be set for the
heat pump operation:
# Code Description
[5.D] [6-01] The temperature difference determining the heat
pump OFF temperature.
Range: 0°C~10°C
Example: setpoint (T
U
)>maximum heat pump temperature–[6‑01] (T
HP MAX
–[6‑01])
INFORMATION
The values indicated in the following graph are examples. For more details about the
DHW operation range of this unit, see the technical data book.