8 | Piping installation
Installer reference guide
88
EPRA14~18D + ETVH/X16S18+23E
Daikin Altherma 3 H HT F
4P644737-1A – 2022.03
a
a Schrader valve
8.1.5 To check the water volume: Examples
Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The
total water volume in the water circuit is 100l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water
volume in the water circuit is 250l.
Actions:
Because the total water volume (250l) is more than the default water volume
(200l), the pre-pressure must be decreased.
The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar = 0.3bar
The corresponding maximum water volume at 0.3bar is 290l. (See the graph in
"Maximum water volume"[486]).
Because 250 l is lower than 290 l, the expansion vessel is appropriate for the
installation.
8.2 Connecting water piping
8.2.1 About connecting the water piping
Before connecting the water piping
Make sure the outdoor and indoor unit are mounted.