8 | Piping installation
Installer reference guide
88
EPRA14~18D + ETVH/X16S18+23E
Daikin Altherma 3 H HT F
4P644737-1A – 2022.03
a Schrader valve
8.1.5 To check the water volume: Examples
Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The
total water volume in the water circuit is 100l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water
volume in the water circuit is 250l.
Actions:
▪ Because the total water volume (250l) is more than the default water volume
(200l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar = 0.3bar
▪ The corresponding maximum water volume at 0.3bar is 290l. (See the graph in
"Maximum water volume"[486]).
▪ Because 250 l is lower than 290 l, the expansion vessel is appropriate for the
installation.