10 | Configuration
Installer reference guide
209
EPRA14~18D + ETVH/X16S18+23E
Daikin Altherma 3 H HT F
4P644737-1A – 2022.03
# Code Description
[9.A.1] [D‑08] Electricity meter 1:
▪ 0 None: NOT installed
▪ 1 1/10kWh: Installed
▪ 2 1/kWh: Installed
▪ 3 10/kWh: Installed
▪ 4 100/kWh: Installed
▪ 5 1000/kWh: Installed
[9.A.2] [D‑09] Electricity meter 2:
▪ 0 None: NOT installed
▪ 1 1/10kWh: Installed
▪ 2 1/kWh: Installed
▪ 3 10/kWh: Installed
▪ 4 100/kWh: Installed
▪ 5 1000/kWh: Installed
In case of pulse meter for photovoltaic panels:
▪ 6 100/kWh for PV panel: Installed
▪ 7 1000/kWh for PV panel: Installed
Sensors
External sensor
# Code Description
[9.B.1] [C–08] External sensor: When an optional external
ambient sensor is connected, the type of the
sensor must be set.
▪ 0 None : NOT installed. The thermistor in the
dedicated Human Comfort Interface and in the
outdoor unit are used for measurement.
▪ 1 Outdoor: Connected to PCB of the indoor
unit measuring the outdoor temperature.
Remark: For some functionality, the
temperature sensor in the outdoor unit is still
used.
▪ 2 Room: Connected to PCB of the indoor unit
measuring the indoor temperature. The
temperature sensor in the dedicated Human
Comfort Interface is NOT used anymore.
Remark: This value has only meaning in room
thermostat control.
Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.