15 | Disposal
Installer reference guide
257
EPRA14~18D + ETVH/X16S18+23E
Daikin Altherma 3 H HT F
4P644737-1A – 2022.03
# Action 7-LEDs display
(a)
H1P H2P H3P H4P H5P H6P H7P
8 Press BS1 once.
H1P keeps flashing, indicating that
you are in a mode that does not
allow compressor operation.
(a)
= OFF, = ON, and = flashing.
Result: The recovery mode is activated. The unit opens the electronic expansion
valves / solenoid valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
# Procedure 7-LEDs display
(a)
H1P H2P H3P H4P H5P H6P H7P
1 Press and hold BS1 for 5seconds.
2 Press BS2 9times.
3 Press BS3 once.
4 Press BS2 once.
5 Press BS3 once.
6 Press BS3 once.
7 Press BS1 once to return to the
default situation.
(a)
= OFF, = ON, and = flashing.
Result: The recovery mode is deactivated. The unit returns the electronic
expansion valves / solenoid valves to their initial state.
INFORMATION
Power OFF. When power is turned OFF and turned ON again, the recovery mode is
deactivated automatically.