4/10
Breadcrumb Field code Setting name Range, step
Default value
Date Value
Installer setting at variance with
default value
Field settings table
└─ WD curve
5.C [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
5.C [0-0C] R/W 45~[6-0E]°C, step: 1°C
60°C
5.C [0-0D] R/W 10~25°C, step: 1°C
15°C
5.C [0-0E] R/W -40~5°C, step: 1°C
-10°C
Tank
5.D [6-01] R/W 0~10°C, step: 1°C
2°C
User settings
└─ Quiet
7.4.1 R/W
0: OFF
1: Quiet
2: More quiet
3: Most quiet
4: Automatic
└─ Electricity price
7.5.1 R/W 0,00~990/kWh
1/kWh
7.5.2 R/W 0,00~990/kWh
1/kWh
7.5.3 R/W 0,00~990/kWh
1/kWh
User settings
7.6 R/W 0,00~990/kWh
0,00~290/MBtu
1,0/kWh
Installer settings
└─ Configuration wizard
└─ System
9.1 [E-03] R/O
3: 6V (*1)
4: 9W
endent
9.1 R/W
0: No
1: Yes
9.1 [1-00] R/W -40~5°C, step: 1°C
-10°C
9.1 [1-01] R/W 10~25°C, step: 1°C
15°C
9.1 [1-02] R/W
[9-01]~[9-00], step: 1°C
35°C
9.1 [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.1 [1-06] R/W 10~25°C, step: 1°C
20°C
9.1 [1-07] R/W
25~43°C, step: 1°C
35°C
9.1 [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C
9.1 [1-09] R/W [9-03]~[9-02]°C, step: 1°C
18°C
└─ Additional zone
9.1 [2-0D] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1 R/W 0: Fixed
1: WD heating, fixed cooling
2: Weather de
endent
9.1 R/W
0: No
1: Yes
9.1 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
50°C
9.1 [0-02] R/W 10~25°C, step: 1°C
15°C
9.1 [0-03] R/W -40~5°C, step: 1°C
-10°C
9.1 [0-04] R/W [9-07]~[9-08]°C, step: 1°C
8°C
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
Gas price
BUH type
Domestic hot water
Leaving water value for high ambient temp. for DHW WD curve.
Emergency
Margin
Activation
High
Medium
Low
Number of zones
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Emitter type
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
Control
Setpoint mode
Schedule
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Schedule
Emitter type
Setpoint mode
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
4P556072-1 - 2018.12 (#) Setting is not applicable for this unit.
(*1) *6V_(*2) *9W_
(*3) *AB*_(*4) EAV*_
(*5) *X*_(*6) *H*_
(*7) EAV*18*_(*8) EAV*23*