Installation manual
23
ERHQ011~016BAV3+W1 + ERLQ011~016CAV3+W1
Outdoor unit for air to water heat pump
4PW57794-1 – 08.2010
18. UNIT SPECIFICATIONS
18.1. Technical specifications
18.2. Electrical specifications
NOTES
ERHQ_V3 ERHQ_W1 ERLQ_V3 ERLQ_W1
Casing material Painted galvanised steel
Dimensions h x w x d (mm)
1170 x
900 x 320
1345 x 900 x 320
Weight (kg) 103 108 114 114
Operation range
• cooling (min./max.)
(°C) 10/46
• heating (min./max.)
(°C)
–20
(a)
/35
(a) See operation range data information sheet for detailed information.
–25
(a)
/35
• domestic hot water
(min./max.)
(°C)
–20
(a)
/35 –25
(a)
/35
Refrigerant oil Daphne FVC68D
Piping connection
• liquid
(mm) 9.52
• gas
(mm) 15.9
V3 W1
Phase 1~ 3N~
Frequency (Hz) 50 50
Voltage range
•minimum
(V) 207 360
•maximum
(V) 253 440