EasyManuals Logo

Daikin ARXG35E3V1B User Manual

Daikin ARXG35E3V1B
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #129 background imageLoading...
Page #129 background image
Check SiBE04-809
118 Service Diagnosis
5.1.4 Thermistor Resistance Check
Check No.06 Remove the connectors of the thermistors on the PCB, and measure the resistance of each
thermistor using tester.
The relationship between normal temperature and resistance is shown in the graph and the
table below.
Thermistor R25°C=20k B=3950
Temperature (°C)
-20 211.0 (k)
-15 150
-10 116.5
-5 88
067.2
551.9
10 40
15 31.8
20 25
25 20
30 16
35 13
40 10.6
45 8.7
50 7.2

Table of Contents