EasyManuals Logo

Daikin B-Series User Manual

Daikin B-Series
352 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
Main Functions Si12-714
60 Function and Control
1.4 Programme Dry Function
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and air flow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
In Case of
Inverter Units
The microcomputer automatically sets the temperature and fan settings. The difference
between the room temperature at startup and the temperature set by the microcomputer is
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Room temperature at
startup
Set temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24ºC or more
Room temperature at
startup
X
2.5ºC
X
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
23.5ºC
X
2.0ºC
X
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
~
18ºC
18ºC X
2.0ºC
X
0.5ºC = 17.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
17.5ºC
~
Z
Y
Zone B
Zone B
Zone A = Thermostat OFF
Zone C = Thermostat ON
+0.5ºC
(R6841)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin B-Series and is the answer not in the manual?

Daikin B-Series Specifications

General IconGeneral
BrandDaikin
ModelB-Series
CategoryInverter
LanguageEnglish

Related product manuals