EDUS39-605 Control Devices
Controls 61
3P166742-2
Mode
No.
Note 1
FIRST
CODE
NO.
Description of setting
SECOND CODE NO. Note 2
01 02 03 04
10(20)
0
Filter Contamination - Heavy/Light are settings
for for spacing of display time to clean air filter:
When filter contamination is heavy, display time
to clean air filter is halved.
Ultra long
life filter
Approx.
10.000
hrs.
Approx.
5.000
hrs.
——
Long life
filter
Approx.
2.500
hrs.
Approx.
1.250
hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
1
Long-life filter type has setting for filter-change indication
time. Change setting when ultra-long filter is installed.
Long-life
filter
Ultra-long
life filter
——
2 Thermostat sensor in remote controller Use Not use — —
3
Display (or not display) time to clean air filter count.
Display
Do not
display
——
12(22)
1
ON/OFF input from outside: Setting for when forced ON/OFF
is to be operated from outside.
Forced OFF
ON/OFF
operation
——
2
Thermostat differential changeover is a setting for when
using remote sensor.
2°F 1°F — —
13(23)
3
Selection of air flow function: Setting for when using a
decoration panel for outlet.
Equipped
Not
equipped
——
4 Air flow direction range setting. Upper Normal Lower —
15(25) 3 Drain pump operation including humidifying. Equipped
Not
equipped
——
1b
0 Permission level setting Level 2 Level 3 — —
1 Away Function
Not
permitted
Permitted — —
2
Thermostat sensor in remote controller is only for lLimit
oOperation and aAway fFunction.
Use Not use — —
Light
Heavy