6 www.daikinac.com SS-DAQ-R32 SS-DAQ-R32 www.daikinac.com 7
Electric Heater Kits
DAQ0903**
and
DAQ1203**
None N/A 208-230/3/60 N/A N/A 15.5 / 15.5 20 / 20
AHKD15-3A 15 208-240/3/60 1 56 54.8-60.6 60 / 70
AHKD20-3A 20 208-240/3/60 2 59 67.3-75.0 70 / 80
AHKD30-3A 30 208-240/3/60 2 60 92.3-104 100 / 110
None N/A 460/3/60 N/A N/A 5.2 15
AHKD15-4A 15 480/3/60 1 55 27.4 30
AHKD20-4A 20 480/3/60 2 57 34.6 35
AHKD30-4A 30 480/3/60 2 58 49.1 50
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon
• These air handlers do not have factory-installed electric heat. The above-listed kits are the ONLY heater kits that
can be used with this commercial series. They are available for purchase as eld-installed accessories.
• The electrical characteriscs of the air handler, electric heater kits, and building power supply must be compable.