6 www.daikinac.com SS-DAX SS-DAX www.daikinac.com 7
Electric Heater Kits
DAX0904**
and
DAX1204**
None N/A 208-240/3/60 N/A N/A 15.5 / 15.5 20 / 20
AHKD15-3A 15 208-240/3/60 1 56 56.3 / 62.4 60 / 70
AHKD20-3A 20 208-240/3/60 2 59 69.4/77.4 70 / 80
AHKD30-3A 30 208-240/3/60 2 60 95.4/108 100 / 110
None N/A 460/3/60 N/A N/A 5.2 15
AHKD15-4A 15 480/3/60 1 55 28.3 30
AHKD20-4A 20 480/3/60 2 57 35.8 40
AHKD30-4A 30 480/3/60 2 58 50.9 60
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon
• These air handlers do not have factory-installed electric heat. The above-listed kits are the ONLY heater kits that
can be used with this commercial series. They are available for purchase as eld-installed accessories.
• The electrical characteriscs of the air handler, electric heater kits, and building power supply must be compable.