29

Main
Menu
Option Menu
Active Alarm menu
Er r Exx
( xx: code numbers )
Last 10 Faults
F10 Exx
( xx: code numbers )
Code Release Number
Cr
CR Number
Reset to Factory Default
r Fd yes, no
Blower Speed for Continuous Fan Mode
FSd Fxx
( xx: Blower Speed Number
F01, F02.. )
Blower Speed for 1st Stage
Compressor Mode
AC1 Fxx
( xx: Blower Speed Number
F01, F02.. )
Blower Speed for 2nd Stage
Compressor Mode
AC2 Fxx
( xx: Blower Speed Number
F01, F02.. )
Cool On Delay
Cnd
Delay, Seconds
Default set at 7 Secs,
Adjustments can be made in
7 Secs increments from 0 to
35 Secs
Cool Off Delay
Cf d
Delay, Seconds
Default set at 65 Secs,
Adjustments can be made in
5 Secs increments from 0 to
120 Secs
Blower Speed for Gas Heat Mode
gAF Fxx
( xx: Blower Speed Number
F01, F02.. )
Gas Heat On Delay
gnd
Delay, Seconds
Default set at 30 Secs,
Adjustments can be made in
5 Secs increments from 5 to
30 Secs
Gas heat Off Delay
gFd
Delay, Seconds
Default set at 90 Secs,
Adjustments can be made in
30 Secs increments from 30 to
180 Secs
Automatic Heat Staging - For Two
Stage Control
AHS
no, 10, 20, 30,
60, AUt
Refer to Section "
CHANGING HEATING
MODE SETTING"
A2L Function Verification
A2u yes, no
Refer to the R-32 Information
Section
A2L Function Enabled
A2E yes, no
Refer to the R-32 Information
Section