3/10
Breadcrumb Field code Setting name Range, step
Default value
Date Value
Field settings table
Installer setting at variance with
default value
3.6 [0-06] R/W 25~43°C, step: 1°C
35°C
3.6 [0-07] R/W 10~25°C, step: 1°C
20°C
Additional zone
3.7 [2-0D] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
3.8.1 [9-05] R/W 15~37°C, step: 1°C
25°C
3.8.2 [9-06] R/W [2-0D]=2:
37~60, step: 1°C
60°C
[2-0D]≠2:
37~55, step: 1°C
55°C
3.8.3 [9-07] R/W 5~18°C, step: 1°C
7°C
3.8.4 [9-08] R/W 18~22°C, step: 1°C
22°C
Additional zone
3.A [C-06] R/W 0: -
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1 [1-0C] R/W [2-0D] ≠2 (Radiator)
3~10°C, step: 1°C
5°C
[2-0D] = 2 (Radiator)
8°C
3.B.2 [1-0E] R/W 3~10°C, step: 1°C
5°C
Space heating / cooling
└─ Operation range
4.3.1 [4-02] R/W 14~35°C, step: 1°C
with BUH:
35°C
without BUH:
25°C
4.3.2 [F-01] R/W 10~35°C, step: 1°C
20°C
Space heating / cooling
4.4 [7-02] R/W
0: 1 LWT zone
1: 2 LWT zones
4.5 [F-0D] R/W 0: Continuous
1: Sample
2: Re
4.7 [9-0D] R/W 0~8, step:1
0 : No limitation
1~4 : 80~50%
5~8 : 80~50% during sampling
6
Space heating / cooling
4.9 [F-00] R/W
0: Restricted
1: Allowed
4.A [D-03] R/W 0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B [9-04] R/W 1~4°C, step: 1°C
4°C
4.C [2-06] R/W 0: Disabled
1: Enabled
User settings
└─ Quiet
7.4.1 R/W 0: OFF
1: Manual
2: Automatic
└─ Electricity price
7.5.1 R/W 0,00~990/kWh
1/kWh
7.5.2 R/W 0,00~990/kWh
1/kWh
7.5.3 R/W 0,00~990/kWh
1/kWh
User settings
7.6 R/W 0,00~990/kWh
0,00~290/MBtu
1,0/kWh
Installer settings
└─ Configuration wizard
└─ System
9.1 [E-03] R/W
0: no BUH
1: External BUH
9.1 [E-05]
[E-06]
[E-07]
R/W
0: No DHW
2: EKHW
7: EKHWP
9.1 [4-06] R/W 0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.1 [7-02] R/W
0: Single zone
1: Dual zone
└─ Backup heater
9.1 [5-0D] R/W
0: 230V, 1~
1: 230V, 3~
2: 400V, 3~
Voltage
Low
Gas price
BUH type
Domestic hot water
Emergency
Number of zones
Increase around 0°C
Overshoot
Room frost protection
Activation
High
Medium
Space cooling OFF temp
Number of zones
Pump operation mode
Unit type
Pump limitation
Pump outside range
Cooling minimum
Cooling maximum
Thermostat type
Delta T heating
Delta T cooling
Space heating OFF temp
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Emitter type
Heating minimum
Heating maximum
(*1) EWAA*
(*2) EWYA*
(#) Setting is not applicable for this unit. 4P627274-1 - 2020.09