4/10
Breadcrumb Field code Setting name Range, step
Default value
Date Value
Field settings table
Installer setting at variance with
default value
9.1 [4-0A] R/W
0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emer
g
enc
y
9.1 [6-03] R/W 0~10kW, step: 0,2kW
0kW
9.1 [6-04] R/W
0~10kW, step: 0,2kW
0kW
└─ Main zone
9.1 [2-0C] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1 [C-07] R/W
0: LWT control
1: Ext RT control
2: RT control
9.1 R/W 0: Fixed
1: WD heating, fixed cooling
2: Weather de
p
endent
9.1 R/W
0: No
1: Yes
9.1 [1-00] R/W -40~5°C, step: 1°C
-10°C
9.1 [1-01] R/W 10~25°C, step: 1°C
15°C
9.1 [1-02] R/W
[9-01]~[9-00], step: 1°C
35°C
9.1 [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.1 [1-06] R/W 10~25°C, step: 1°C
20°C
9.1 [1-07] R/W
25~43°C, step: 1°C
35°C
9.1 [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C
9.1 [1-09] R/W [9-03]~[9-02]°C, step: 1°C
18°C
└─ Additional zone
9.1 [2-0D] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1 R/W 0: Fixed
1: WD heating, fixed cooling
2: Weather de
p
endent
9.1 R/W
0: No
1: Yes
9.1 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
55°C
9.1 [0-02] R/W 10~25°C, step: 1°C
15°C
9.1 [0-03] R/W -40~5°C, step: 1°C
-10°C
9.1 [0-04] R/W [9-07]~[9-08]°C, step: 1°C
18°C
9.1 [0-05] R/W [9-07]~[9-08]°C, step: 1°C
22°C
9.1 [0-06] R/W 25~43°C, step: 1°C
35°C
9.1 [0-07] R/W 10~25°C, step: 1°C
20°C
└─ Tank
9.1 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
9.1 [6-0A] R/W 30~[6-0E]°C, step: 1°C
50°C
9.1 [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
9.1 [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
└─ Domestic hot water
9.2.1 [E-05]
[E-06]
[E-07]
R/W
0: No DHW
2: EKHW
7: EKHWP
9.2.2 [D-02] R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circulation Pump
4: Circulation Pum
p
and disinf. Shunt
9.2.4 [D-07] R/W
0: No
1: Yes
└─ Back up heater
9.3.1 [E-03] R/W
0: no BUH
1: External BUH
9.3.2 [5-0D] R/W
0: 230V, 1~
1: 230V, 3~
2: 400V, 3~
9.3.3 [4-0A] R/W
0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emer
g
enc
y
9.3.4 [6-03] R/W 0~10kW, step: 0,2kW
0kW
9.3.5 [6-04] R/W
0~10kW, step: 0,2kW
0kW
9.3.6 [5-00] R/W 0: Allowed
1: Not allowed
9.3.7 [5-01] R/W -15~35°C, step: 1°C
0°C
9.3.8 [4-00] R/W 0: Disabled
1: Enabled
2: Onl
y
DHW
Configuration
Capacity step 1
Additional capacity step 2
Equilibrium
Equilibrium temperature
Operation
Reheat setpoint
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Heat up mode
Comfort setpoint
Eco setpoint
Schedule
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Emitter type
Setpoint mode
Setpoint mode
Schedule
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Configuration
Capacity step 1
Additional capacity step 2
Emitter type
Control
4P627274-1 - 2020.09 (#) Setting is not applicable for this unit.
(*1) EWAA*
(*2) EWYA*