EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075 - R410A - Air-cooled scroll chillers
EWAQ- - R410A - Air-cooled scroll chillers
EWYQ- - R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
1.6 Abbreviations used
In this manual, the refrigeration circuits are called circuit #1 and circuit #2.
The following abbreviations are used frequently:
Condensing Saturated Refrigerant Temperature
Evaporating Saturated Refrigerant Temperature
Electronic Expansion Valve
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
Condenser Leaving Water Temperature
Condenser Entering Water Temperature
1.7 Customer Terminal Block Connections
1.7.1 Connections description and purpouse
The contacts below are available at the user’s terminal block referred as MC24 or MC230 in the
wiring diagram. The following table summarizes the connections at the user’s terminal block.
Evaporator Flow Switch (mandatory)
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
Condenser Flow Switch (W/C
mandatory)
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
Cooling/Heating Remote switch (H/P
units only)
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
NO digital output (24…230 Vac ext supply)
NO digital output (24…230 Vac ext supply)
Evaporator Pump #2 start (A/C only)
NO digital output (24…230 Vac ext supply)
Evaporator Pump #2 start (W/C only)
NO digital output (24 Vdc - 25mA )