LWT setpoint can also be set via network if the appropriate control source has been selected.
Setpoint range is limited according to the selected operating mode. The controller includes two
setpoint in cooling mode (either standard cool or cool w/glycol) and one setpoint in ice mode, which
are activated according to Operating mode and Dual Setpoint selection. All default setpoint with
their ranges are reported in the table below.
The LWT setpoint can be overridden in case the setpoint reset (for details see chapter 5.1.7.2).
Double Setpoint, Setpoint Reset features are not operational in Ice Mode.
5.1.4 Thermostat Control Settings
Thermostat control settings allow to set up the response to temperature variations and the
precision of the thermostat control. Default settings are valid for most applications, however site
specific conditions may require adjustments in order to have a smooth and precise temperature
control or a quicker response of the unit. The parameters mentioned below can be set from the
menu 4.2.1
The following explanation can be read for Chiller/Heat Pump modes.
Compressors start conditions. The control will start the first compressor if the controlled
temperature is higher/lower than the active setpoint of at least a Start Up DT value. The other
compressors will start, one at a time, if the controlled temperature is higher/lower than the active
setpoint of at least Stage Up DT value.
Compressors shutdown conditions. The control will shut down the compressors, one at a time,
if the controlled temperature is lower/higher than the active setpoint of at least Stage Down DT
value. Last compressor in run will shut down if the controlled water temperature is lower/higher
than the active setpoint of at least Shut down DT value.
Temperature Limitation. The start-up and shut-down of all compressors are inhibited if the
controlled water temperature decreases/increases faster than Pull Down Rate/Pull Up Rate limit
value.
Time Limitation. The start-up and shut-down of each compressor must respect the following time
constrains.
1. A compressor can start only if since the last start-up or shut-down of any other compressor
the Stage Up Delay has expired.