Low pressure unload limit
High pressure unload limit
High pressure alarm limit
2.0…5.6°C (without
Glycol)
-20.0…5.6°C (with
Glycol)
Evaporator freeze protection limit
2.0…5.6°C (without
Glycol)
-20.0…5.6°C (with
Glycol
Condenser freeze protection limit (W/C only)
Recirculating timeout before the alarm is raised
Start time during which the low pressure alarm is ignored.
Minimum pressure difference to trigger the Low Delta Pressure alarm
Once tripped, the software will get back to normal operation. However, the alarm will not be reset
until the high pressure switches are manually reset through the button included in the switch.
4.9.3 Calibrate Unit Sensors
This page allows a proper calibration of the unit sensors.
Evaporator LWT current reading (includes the offset)
Evaporator LWT calibration
Evaporator EWT current reading (includes the offset)
Evaporator EWT calibration
Condenser LWT current reading (includes the offset) (W/C only)
Condenser LWT calibration (W/C only)
Condenser EWT current reading (includes the offset) (W/C only)
Condenser EWT calibration (W/C only)
Oustide Air Temperature current reading (includes the offset) (A/C only)
Oustide Air Temperature calibration (A/C only)
4.9.4 Calibrate Circuit Sensors
This page allows a proper calibration of the circuit sensors
Evaporator Pressure current reading (includes the offset)
Evaporator Pressure offset
Condenser Pressure current reading (includes the offset)
Condenser Pressure offset
Suction Temperature current reading (includes the offset)
Suction Temperature offset
Discharge Temperature current reading (includes the offset) (A/C only)
Discharge Temperature offset (A/C only)
Calibrations of the Evaporator Pressure and Suction Temperature are mandatory for the
applications with negative water temperature setpoints. These calibrations have to be performed
with proper gauge and thermometer.
An improper calibration of the two instruments may generate limitation of the operations, alarms
and even damages to components.