3.5 Basic Control System Diagnostic
Unit controller, extension modules and communication modules are equipped with two status LED
(BSP and BUS) to indicate the operational status of the devices. The BUS LED indicates the status
of the communication with the controller. The meaning of the two status LED is indicated below.
UC BSP LED
Application loaded but not running (*) or BSP Upgrade mode active
BSP startup phase. The controller needs time for starting.
Application not loaded (*)
Fail safe mode (in case that the BSP upgrade was interrupted)
BSP Error (software error*)
Application/BSP update or inizialization
(*) Contact Service.
Extension modules
BSP LED
BUS LED
Communication running, I/O working
Communication running but parameter from the application wrong or missing, or uncorrect factory calibration
Communication modules
BSP LED (same for all modules)
BPS running, communication with controller
BSP running, no communication with controller (*)
(*) Contact Service.
LON module BUS LED
Ready for Communication. (All Parameter loaded, Neuron configured). Doesn't indicate a communication
with other devices.
No Communication to Neuron (internal error, could be solved by downloading a new LON application)
Communication not possible to the Neuron. The Neuron must be configured and set online over the LON
Tool.
Bacnet MSTP BUS LED
Ready for Communication. The BACnet Server is started. It doesn't indicate a active communication
BACnet Server down. Automatically a restart after 3 seconds are initiated.