4 Menu Structure
All settings are divided in different menus. Each menu collects in a single page other sub-menus,
settings or data related to a specific function (for example Power Conservation or Setup) or entity
(for example Unit or Circuit). In any of the following pages a grey box will indicate changeable
values and the defaults.
4.1 Main Menu
Setpoint/Sub-Menu
Default
Range
Description
Enter Password
-
Submenu to activate access levels
View/Set Unit
-
Submenu for unit data and settings
View/Set Circuit
-
Submenu for circuit data and settings
Unit Status=
Off: Unit Loc/Rem Sw
Auto
Off: Ice Mode Tmr
Off: All Cir Disabled
Off: Unit Alarm
Off: Keypad Disable
Off: BAS Disable
Off: Unit Loc/Rem Sw
Off: Test Mode
Auto: Wait For Load
Auto: Evap Recirc (A/C only)
Auto Water Recirc (W/C only)
Auto: Wait For Flow
Auto: Pumpdn
Auto: Max Pull Limited
Auto: Unit Cap Limit
Off: Cfg Chg, Rst Ctrlr
Status of the Unit
Active Setpt=
7.0°C
-
Active setpoint and link to the
Setpoint page (see section 4.3.1.5 for
more details).
Evap LWT=
-273.1°C
-
Evaporator leaving water
temperature and link to the
Temperatures page (see section 4.5
for more details).
Cond LWT=
-273.1°C
-
Condenser leaving water
temperature and link to the
Temperatures page (W/C only).
Unit Capacity=
0.0%
-
Actual unit capacity.
Chiller Enable=
Enable
Enable-Disable
Chiller operation enable/disable
setting.
Unit Mode=
Cool
-
Actual unit mode and link to unit
available mode selection page (see
section 4.6 for more details).
Timers
-
Submenu compressors and
thermoregulation safety timers (see
section 4.7 for more details).
Alarms
-
Submenu for alarms; same function
as Bell Button (see section 0 for more
details)
Commission Unit
-
Submenu for the chiller configuration
(see section 0 for more details).
Save and Restore
Submenu to the Save and Restore
page (see section
About Chiller
-
Application Info submenu (see
section 0 for more details).