EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- - R410A - Air-cooled scroll chillers
EWAQ- - R410A - Air-cooled scroll chillers
EWYQ- - R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
4.9.1 Configure Unit
This page resumes all the specific settings for this unit like unit type, number of circuits, type of
condensing control, etc.. Part of these settings cannot be adjusted and are supposed to be set
during the manufacturing or commissioning of this unit. The modification of each parameter in this
menu requires that the unit switch is set to 0.
Select the unit type, chiller (EWWD) or condenser less (EWLD) (W/C only)
Select the unit type basing on the model name.
Selects between the two noise class. (A/C C/O only)
Number of circuit of the chiller
Type of inversion in heat pump mode. (W/C only)
No, Pressure,
Cond In, Cond
Out
Enabling of the condensing control (W/C only)
Select device type used for condensing control (W/C only)
Standalone,
Master, Slave 1 ,
Slave 2, Slave 3
Define if the chiller works as standalone or belongs to Master Slave
network,
Indicate the number of chiller belonging to Master Slave network. This
parameter have to be set only in the chiller Master, in all Slave units it can
be let at default value as ignored.
Define the sensor type used to measure the common leaving water
temperature.
This parameter have to be set only in the chiller Master, in all Slave units it
can be let at default value as ignored.
Behavior of the unit alarm digital output
Enabling of the phase voltage monitor
Enabling of the Event or External Alarm input.
Enabling of the Demand Limit signal
Enabling of the Lwt Reset signal
None, IP, Lon,
MSTP, Modbus,
AWM
Auto-configured when UC link with related module
Modbus, Bacnet
IP, Bacnet MSTP,
Lon, AWM
Auto-configured when UC link with related module
Modbus, Bacnet
IP, Bacnet MSTP,
Lon, AWM
Auto-configured when UC link with related module
Modification to any of these values will require to be acknowledged to the controller by setting
“Apply Changes = Yes”. This will cause a controller reboot! This action can only be performed with
the Q0 switch on the unit switchbox set to 0.
4.9.2 Alarm Limits
This page contains all alarm limits, including low pressure alarm prevention thresholds. In order to
ensure proper operation they have to be set manually according to the specific application.