EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- - R410A - Air-cooled scroll chillers
EWAQ- - R410A - Air-cooled scroll chillers
EWYQ- - R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Start Up / Shut Down priority of the chiller Master
Priority = 1 highest priority
Priority = 4 lowest priority
Start Up / Shut Down priority of the chiller Slave 1
Priority = 1 highest priority
Priority = 4 lowest priority
Start Up / Shut Down priority of the chiller Slave 2.
Priority = 1 highest priority
Priority = 4 lowest priority
This menu is visible only if the parameter M/S Num Of Unit has been configured at
least with value 3
Start Up / Shut Down priority of the chiller Slave 3.
Priority = 1 highest priority
Priority = 4 lowest priority
This menu is visible only if the parameter M/S Num Of Unit has been configured at
least with value 4
Parameter is used to disable the Master Chiller
4.2.5.3 Thermostat control
The parameters changeable with this menu, available only in the unit configured as Master, are
related to the thermoregulation of all Master Slave system.
Offset respect the active setpoint for the unit startup.
Offset respect the active setpoint for the unit shutdown.
Threshold of load that have to reach all units running before allow the startup of a
new chiller
Minimum time between the start of two chillers
Minim time between the stop of two chillers
4.2.5.4 Data
In this menu, available only in the unit configured as Master, are collected all main data related to
the Master Slave function.
-,Master, Slave 1, Slave 2,
Slave 4
Display next chiller that will be starts
-,Master, Slave 1, Slave 2,
Slave 4
Display next chiller that will be stopped
-,Master, Slave 1, Slave 2,
Slave 4
Display the actual standby chiller
Display the day and the time in the day when will be performed the
rotation of the sandby chiller
Display the actual state of the Master
Display the actual state of the Slave 1
Display the actual state of the Slave 2
Display the actual state of the Slave 3
Display the actual load of the Master
Display the actual load of the Slave 1
Display the actual load of the Slave 2
Display the actual load of the Slave 3