4-20 mA Analog input singal
Setpoint Reset by Evaporator Return Temperature
The active setpoint is calculated applying a correction that depends on the evaporator entering
(return) water temperature
If the unit works in heat pump mode with water inversion the correction depends on the condenser
entering (return) water temperature (W/C only).
When the evaporator/condenser ΔT becomes lower than the SRΔT value, an offset to the LWT
setpoint is increasingly applied, up to the MR value when the ΔT is equal to zero
The Return Reset may affect negatively the chiller operation when operated with variable
flow. Avoid to use this strategy in case of inverter water flow control.
Setpoint Reset by Outside Air Temperature (OAT) (A/C only)
The active setpoint is calculated applying a correction that depends on the outside air temperature.