Daikin F-Series - Input over Current Detection

Daikin F-Series
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiBE12-713 Troubleshooting
Service Diagnosis 253
5.15 Input Over Current Detection
Remote
Controller
Display
E8
Outdoor Unit LED
Display
A
5
1
1
2
4
3
1
4
4
Method of
Malfunction
Detection
Malfunction is detected by checking the input current value.
Malfunction
Decision
Conditions
The following condition continues for 2.5 seconds.
Input current
20A (typical value)
The compressor halts if the error occurs, and restarts automatically after 3 minutes stand-by.
Supposed
Causes
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective inverter main circuit electrolytic capacitor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit