EasyManua.ls Logo

Daikin F-Series - Thermostat Control

Daikin F-Series
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Main Functions SiBE12-713
68 Function and Control
1.7 Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference is above the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Wall Mounted Type
Floor standing Type
Floor/Ceiling suspended Type
Duct Connected Type
Heating
Wall Mounted Type
Floor standing Type
Floor/Ceiling suspended Type
Duct Connected Type
B
A
OFF
ON
C
Cooling : – 0.5˚C
Dry : – 0.5˚C
Room temperature - setpoint
Cooling : – 2.0˚C
Dry : – 2.5~– 2.0˚C
(R4668)
B
A
OFF
ON
C
– 1.5˚C
Room temperature - setpoint
Cooling : – 2.0˚C
Dry : – 2.5~– 2.0˚C
Cooling : – 1.0˚C
Dry : – 1.0˚C
(R6032)
B
A
OFF
ON
C
1.5˚C
Room temperature - setpoint
0˚C
(R4669)
B
A
OFF
ON
C
1.5˚C
1.0˚C
Room temperature - setpoint
0.5˚C
(R6033)

Table of Contents

Other manuals for Daikin F-Series

Related product manuals