18 | Electrical installation
Installer and user reference guide
69
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Wire type Installation method
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
Wiring Screw size Tightening torque
(N•m)
Interconnection cable
(indoor↔outdoor)
M4 1.18~1.44
User interface cable M3.5 0.79~0.97
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
18.1.3 Specifications of standard wiring components
Component Specification
Interconnection cable (indoor↔outdoor) 4-core cable 1.5mm
2
~2.5mm
2
and
applicable for 220~240V
H05RN-F (60245 IEC 57)
(a)
User interface cable Vinyl cords with 0.75 to 1.25mm²
sheath or cables (2‑core wires)
H03VV-F (60227 IEC 52)
Maximum 500m
(a)
In case the conduit pipes are not used, use H07RN-F (60245 IEC 66).
18.2 To connect the electrical wiring to the indoor unit
NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.