18
Engineering & Physical Data
Safety Device
MODEL
INDOOR FCRN18FXV1S FCRN24FXV1S FCRN30FXV1S
OUTDOOR RN18CXV1S2 RR24CXV1S2 RR30CXV1S2
SAFETY
DEVICE
HIGH
PRESSURE
SWITCH
TYPE N/A N/A N/A
OPEN kPa / psi N/A N/A N/A
CLOSE kPa / psi N/A N/A N/A
LOW
PRESSURE
SWITCH
TYPE N/A N/A N/A
OPEN kPa / psi N/A N/A N/A
CLOSE kPa / psi N/A N/A N/A
PHASE SEQUENCER N/A N/A N/A
DISC. THERMOSTAT
SETTING
°C / F N/A N/A N/A
MODEL
INDOOR FCRN36FXV1S FCRN42FXV1S FCRN45FXV1S
OUTDOOR RR36DXV1S2 RR42DXY1S2 RR45DXY1S2
SAFETY
DEVICE
HIGH
PRESSURE
SWITCH
TYPE NC NC NC
OPEN kPa / psi 4140/600 4140/600 4140/600
CLOSE kPa / psi 3310/480 3310/480 3310/480
LOW
PRESSURE
SWITCH
TYPE NC NC NC
OPEN kPa / psi 48/7 48/7 48/7
CLOSE kPa / psi 152/22 152/22 152/22
PHASE SEQUENCER N/A YES YES
DISC. THERMOSTAT
SETTING
°C / F N/A 130/266 130/266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.