FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
189
3P572321-4B
12
[For wireless remote controller]
1) Press
and select the COOL operation.
2) Press
twice. “Test” is displayed.
3) Press
within 10 seconds, and the forced cooling operation starts.
Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press
.
[For FTX models]
Using the indoor unit ON/OFF switch
Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)
Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.
Using the indoor unit’s remote controller
1) Press
and select the COOL operation.
2) Press
to turn on the system.
3) Press
, and at the same time.
4) Press
, select “ ”, and press forconrmation.
Forced cooling operation will stop automatically after about 30 minutes. To stop the operation, press .
Trial Operation and
Testing
When trial operation is conducted directly after the circuit breaker is turned on, in some cases no air will be output for about 15
minutes in order to protect the air conditioner.
1. Trial operation and testing
Refer to the installation manual for the indoor unit.
2. Test items
Test items Symptom Check
Indoor and outdoor units are installed securely. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/heating function
Refrigerantgasandliquidpipesandindoordrainhoseextensionare
thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
System is properly grounded. Electricalleakage
Thespeciedwiresareusedforinter-unitwiring. No operation or burn damage
Indoor or outdoor unit’s air inlet or air outlet are unobstructed. Incomplete cooling/heating function
Stop valves are opened. Incomplete cooling/heating function
Indoor unit properly receives remote control commands. No operation
01_EN_3P572321-4B.indd 12 2019/10/17 14:47:00

Table of Contents

Other manuals for Daikin FDMQ-R Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FDMQ-R Series and is the answer not in the manual?

Daikin FDMQ-R Series Specifications

General IconGeneral
BrandDaikin
ModelFDMQ-R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals