FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
79
C: 3P379970-5B
9
Refrigerant Piping Work
1� Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward,
so that the lings do not enter the pipe.
3) Put the are nut on the pipe.
4) Flare the pipe.
5) Check that the aring has been done correctly.
Set exactly at the position shown below.
Flaring
A
A
0-0.020 inch
(0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch
(1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch
(1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional are tool
Remove burrs.
Cut exactly at
right angles.
Check
The are's inner
surface must be
aw-free.
The pipe end must
be evenly ared in
a perfect circle.
Make sure that the
are nut is tted.
Die
WARNING
• Do not apply mineral oil to the are.
• Prevent mineral oil from getting into the system as this would reduce the service life of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
• Never install a dryer to this R410A unit in order to guarantee its service life.
• The drying material may dissolve and damage the system.
• Incomplete aring may result in refrigerant gas leakage.
2� Refrigerant piping
CAUTION
• Use the are nut xed to the main unit. (This is to prevent the are nut from cracking as a result of deterioration over time.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the are. (Use refrigeration oil for R410A.)
• Use a torque wrench when tightening the are nuts to prevent damage to the are nuts and gas leakage.
• Align the centers of both ares and tighten the are nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a
torque wrench.
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration
oil to the inner
surface of the are.
Do not apply refrigeration oil to
the are nut to avoid tightening
with excessive torque.
Apply oil
Torque wrench
Piping union
Flare nut
Spanner
Tighten
Gas side
Piping size
O.D.
3/8 inch
(9.5mm)
O.D. 1/2 inch
(12.7mm)
O.D. 5/8 inch
(15.9mm)
O.D. 1/4 inch
(6.4mm)
24-1/8 – 29-1/2ft • Ibf
(32.7-39.9N • m)
36-1/2 – 44-1/2ft • lbf
(49.5-60.3N • m)
45-5/8 – 55-5/8ft • Ibf
(61.8-75.4N • m)
10-1/2 – 12-3/4ft • lbf
(14.2-17.2 N • m)
Flare nut tightening torque
Liquid side
2-1� Caution on piping handling
• Protect the open end of the pipe against dust and moisture.
• All pipe bends should be as gentle as possible. Use a pipe bender
for bending.
Wall
If no are cap is
available, cover
the are mouth
with tape to keep
dirt and water out.
Be sure to
place a cap.
Rain
01_EN_3P379970-5B.indd 9 10/29/2015 16:21:04

Table of Contents

Other manuals for Daikin FDMQ-R Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FDMQ-R Series and is the answer not in the manual?

Daikin FDMQ-R Series Specifications

General IconGeneral
BrandDaikin
ModelFDMQ-R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals