Check SiUS041829E
112 Part 6 Service Diagnosis
5. Check
5.1 Thermistor Resistance Check
Check No.01 Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance between
the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
R6000517
Multimeter
Resistance range
Thermistor ASSY Soldered thermistor
Multimeter
Thermistor temperature Resistance (kΩ)
(°C) (°F)
R (25°C (77°F)) = 20 kΩ
B = 3950 K
–20 –4 197.8
–15 5 148.2
–10 14 112.1
–5 23 85.60
0 32 65.93
5 41 51.14
10 50 39.99
15 59 31.52
20 68 25.02
25 77 20.00
30 86 16.10
35 95 13.04
40 104 10.62
45 113 8.707
50 122 7.176
(kΩ)
150
100
50
–15 0 15 30 45
(R14467)
5 32 59 86 113
(°C)
(°F)

Table of Contents

Other manuals for Daikin FTXR-T Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTXR-T Series and is the answer not in the manual?

Daikin FTXR-T Series Specifications

General IconGeneral
BrandDaikin
ModelFTXR-T Series
CategoryHeat Pump
LanguageEnglish

Related product manuals