EasyManua.ls Logo

Daikin FTXS60GV1B - Fan Motor (DC Motor) or Related Abnormality

Daikin FTXS60GV1B
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting SiBE041011_A
66 Service Diagnosis
4.4 Fan Motor (DC Motor) or Related Abnormality
Error Code
A6
Method of Error
Detection
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Error Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB

Table of Contents

Other manuals for Daikin FTXS60GV1B

Related product manuals