Troubleshooting SiENBE28-901
104 Air Cooled Refrigeration Condensing Unit
6.6.11
H7
” Abnormal Outdoor Fan Motor Signal
Remote
Controller
Display
H7
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Detection of abnormal signal from fan motor.
Malfunction
Decision
Conditions
In case of detection of abnormal signal at starting fan motor.
Supposed
Causes
Abnormal fan motor signal (circuit malfunction)
Broken, short or disconnection connector of fan motor connection cable
Fan Inverter PCB malfunction (A4P or A8P)