EasyManua.ls Logo

Daikin LRLEQ5AY1(E) - Flow Chart for Troubleshooting

Daikin LRLEQ5AY1(E)
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting SiENBE28-901
84 Air Cooled Refrigeration Condensing Unit
6.6 Flow Chart for Troubleshooting
6.6.1
E0
” STD Compressor Motor Overcurrent/Lock
Remote
Controller
Display
E0
Applicable
Models
LRMEQ8~20AY1
LRLEQ8~20AY1
Method of
Malfunction
Detection
Detects the overcurrent with current sensor (CT).
Malfunction
Decision
Conditions
Malfunction is decided when the detected current value exceeds 14.95A for 2 seconds.
Supposed
Causes
Closed stop value
Obstacles at the air outlet
Improper power voltage
Faulty magnetic switch
Faulty compressor
Faulty current sensor (A6P, A7P)
Defect of outdoor unit PCB (A1P)

Related product manuals