Standard Specification SiENBE28-901
14 Air Cooled Refrigeration Condensing Unit
2.3 Operation Limits
LRLEQ5, 6, 8, 10, 12, 15, 20AY1(E)
LRMEQ5, 6, 8, 10, 12, 15, 20AY1(E)
NOTES
1. “Range for continuous operation” SHOWS POSSIBLE RANGE OF CONTINUOUS OPERATION.
2. “Range for pull down operation” SHOWS POSSIBLE RANGE OF SHORT-TIME OPERATION.
Outdoor temperature (°CDB)
43
Range for continuous operation
Range for pull down operation
Evaporating temperature (°C)
4D064913
40
35
30
25
20
15
10
5
-10
-5
0
-15
-45 -40 -35 -30 -25 -20 -15 5 10 30 35 40
DO NOT SELECT THE MODEL IN THE RANGE FOR PULL DOWN OPERATION.
TO BE MORE THAN 3°C/HOUR THAT THE TEMPERATURE OF INDOOR UNIT DROPS.
DO NOT OPEN THE DOOR AND DO NOT ENTER THE GOODS IN PULL DOWN OPERATION AS
MUCH AS.
Outdoor temperature (°CDB)
Range for continuous operation
Range for pull down
operation
43
40
35
30
25
20
15
10
5
-10
-5
0
-15
-20 -15 5 10 30 35 400
-10 -5
Evaporating temperature (°C)
4D064914