SiENBE28-901 Description of Functions and Operation
Air Cooled Refrigeration Condensing Unit 51
(3)-1. Compressor steps table
INV
step
General
step
INV
compressor
frequency (Hz)
INV
step
General
step
INV compressor
frequency (Hz) +
the number of
STD compressors
INV
step
General
step
INV compressor
frequency (Hz) +
the number of
STD compressors
0 0 0 1 21 52+STD×1 1 41 52+STD×2
1 1 52 2 22 56+STD×1 2 42 56+STD×2
2 2 56 3 23 62+STD×1 3 43 62+STD×2
3 3 62 4 24 68+STD×1 4 44 68+STD×2
4 4 68 5 25 74+STD×1 5 45 74+STD×2
5 5 74 6 26 80+STD×1 6 46 80+STD×2
6 6 80 7 27 88+STD×1 7 47 88+STD×2
7 7 88 8 28 96+STD×1 8 48 96+STD×2
88 96
8,10,12,
15,20AY1
929
104+STD×1
(15,20AY1)
949
104+STD×2
9 9 104 10 30
110+STD×1
10 50
110+STD×2
10 10 110 11 31
116+STD×1
11 51
116+STD×2
11 11 116 12 32
124+STD×1
12 52
124+STD×2
12 12 124 13 33
132+STD×1
8AY1 13 53
132+STD×2
13 13 132 14 34
144+STD×1
14 54
144+STD×2
14 14 144 15 35
158+STD×1
15 55
158+STD×2
15 15 158 5AY1 16 36
165+STD×1
16 56
165+STD×2
16 16 165 17 37
176+STD×1
17 57
176+STD×2
17 17 176 18 38
188+STD×1
18 58
188+STD×2
15AY1
18 18 188 19 39
202+STD×1
10AY1 19 59
202+STD×2
19 19 202 20 40
210+STD×1
20 60
210+STD×2
20 20 210 21 41
218+STD×1
21 61
218+STD×2
21 21 218 6AY1 22 42
232+STD×1
12AY1 22 62
232+STD×2
20AY1

Related product manuals