EasyManuals Logo
Home>Daikin>Inverter>LX10F11B3

Daikin LX10F11B3 User Manual

Daikin LX10F11B3
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
2-41
102 F52E F52F F53B
E52D E52E E52F
Alarm
Logic
&
Possible
Causes
Alarm Logic Possible Causes
E52DFin temperature sensor failure Inverter board failureFin temperature sensor
Fin temperature150 or -45≦℃)
F52EE52E is generated 4 times.
E52EOver current failure
Inverter board failureIPM part
IPMIntelligent Power Module
F52FE52F is generated 4 times.
E52FCompressor current sensor failure
Inverter board failureCurrent detection part
F53BEEPROM failure when unit is on Inverter board failure (EEPROM part)
EEPROM : Electrically Erasable Program ROM
Trouble
Shooting
Replace Inverter board
Controller
Action
F52E, F52F, F53B Unit stop
E52D Restart after 3 minutes
E52E, E52F Restart after 3 minutes (F52E, F52F is generated at 4 times retry.
02章19-44LX10F11B3TR16-02En.indd2-4102章19-44LX10F11B3TR16-02En.indd2-41 2016/02/0217:17:422016/02/0217:17:42
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B3 and is the answer not in the manual?

Daikin LX10F11B3 Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B3
CategoryInverter
LanguageEnglish

Related product manuals