2-41
102 F52E F52F F53B
E52D E52E E52F
Alarm
Logic
&
Possible
Causes
Alarm Logic Possible Causes
E52DFin temperature sensor failure Inverter board failureFin temperature sensor
Fin temperature150 or -45≦℃)
F52EE52E is generated 4 times.
E52EOver current failure
Inverter board failureIPM part
IPMIntelligent Power Module
F52FE52F is generated 4 times.
E52FCompressor current sensor failure
Inverter board failureCurrent detection part
F53BEEPROM failure when unit is on Inverter board failure (EEPROM part)
EEPROM : Electrically Erasable Program ROM
Trouble
Shooting
Replace Inverter board
Controller
Action
F52E, F52F, F53B Unit stop
E52D Restart after 3 minutes
E52E, E52F Restart after 3 minutes (F52E, F52F is generated at 4 times retry.
02章19-44LX10F11B3TR16-02En.indd2-4102章19-44LX10F11B3TR16-02En.indd2-41 2016/02/0217:17:422016/02/0217:17:42