2-43
106 E52C
Alarm
Logic
Inverter board temperature is over-heated (90 with 260 sec elapse or 99 with 5 sec
elapse)
Possible
Causes
Ambient temperature is high>50℃)
Inverter board failure fin temperature detection part
Inverter box is heat up due to less air circulation.
Trouble
Shooting
The unit can operate with an ambient temperature of up to 50 .
Check for a short circuit at the discharge air of the air cooling condenser coil and also check
the surrounding environment. Operation continues if the environment is improved.
If no external factors are present, the inverter board may have failed. Replace the inverter
board.
Clean the fin on the rear of the inverter box and the base of the inverter box to ensure that
the air can circulate.
E52CRestart after 3 minutes
107 E531
Alarm
Logic
Unbalanced power phase is supplied
Possible
Causes
Abnormal power supply
Trouble
Shooting
Regardless alarm is generated, restart after 3 minutes standby.
Operation continues if the external factor is improved.
E531Restart after 3 minutes
108 E532
Alarm
Logic
Voltage in inverter becomes DC790V or DC320V due to power supply voltageAC530V or
AC300V.
Possible
Causes
Power supply voltage is at high voltage (AC535V), or low voltage (AC300V).
Inverter board failure (Voltage detection part)
Trouble
Shooting
Check if the actual power voltage is within range (300V535V.
Provide the power supply within range if it is out of range.
Restart after 3 minutes standby.
Operation continues if the power supply condition is improved.
If the power voltage is within range, it seems to be inverter board failure. Replace inverter
board.
Controller
Action
E532Restart after 3 minutes
02章19-44LX10F11B3TR16-02En.indd2-4302章19-44LX10F11B3TR16-02En.indd2-43 2016/02/0217:17:422016/02/0217:17:42
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B3 and is the answer not in the manual?

Daikin LX10F11B3 Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B3
CategoryInverter
LanguageEnglish

Related product manuals